PVC Insulated, 2 Core + E Flat Cables, 450/750V

Application

These cables are used for general wiring, unenclosed, enclosed in conduit, buried direct or in underground ducts for domestic, commercial and industrial installations where not subject to mechanical damage. Suitable for single phase applications requiring neutral and E.

Standard

  • AS/NZS 5000.2
  • AS 1125
  • AS 3808

Cable Construction

CONDUCTOR Plain annealed copper
Maximum operating temperature: 90°C
INSULATION PVC V90
INSULATION COLOUR: Red, Black, Green/yellow
SHEATH: Polyvinylchloride compound PVC 3V90
SHEATH COLOUR: White, other colors are available upon request

Technical Characteristics

PVC Insulated, 2 Core + E Flat Cables

NOMINAL AREA MM2 CURRENT RATINGS ELECTRICAL CHARACTERISTICS
UNENCLOSED IN AIR
A
SURROUNDED BY THERMAL INSULATION A BURIED IN DUCTS
A
MAXIMUM
DC
RESISTANCE
@20°C
OHM/KM
MAXIMUM AC RESISTANCE
@75°C
OHM/KM
REACTANCE OHM/KM SINGLE
PHASE VOLTAGE DROP MV/AM
1 16 8 19 18.1 27.0 0.119 54.1
1.5 21 10 24 13.6 17.3 0.111 34.7
2.5 30 15 34 7.41 9.45 0.102 19.0
4 39 19 44 4.61 5.88 0.102 11.8
6 50 25 56 3.08 3.93 0.0967 7.9
10 68 34 75 1.83 2.33 0.0906 4.7
16 91 46 97 1.15 1.47 0.0861 2.95

Cable Parameter

NOM.
CONDUCTOR AREA MM2
CONDUCTOR NO./ OD NOM.
INSULATION THICKNESS MM
EARTH
CONDUCTOR AREA MM2
NOM. SHEATH THICKNESS MM NOM. OVERALL DIAMETER
MM
APPROX. MASS KG/KM
MIN MAX
1.0 1/1.13 0.6 1.0 0.9 8.8x4.1 9.3x4.4 75
1.5 7/0.50 0.6 1.5 0.9 10.0x4.5 10.0x4.5 95
2.5 7/0.67 0.7 2.5 1 12.1x5.4 12.7x5.7 145
4 7/0.85 0.8 2.5 1.1 13.7x6.3 14.4x6.6 220
6 7/1.04 1.0 2.5 1.1 14.9x6.9 15.6x7.3 290
10 7/1.35 1.0 4 1.2 18.9x8.3 19.0x8.7 440
16 7/1.70 1.0 6 1.3 21.0x9.5 22.0x10.0 645